9 Troubleshooting
9-1
Types of Errors
The Reader/Writer indicates errors in the following ways.
• Errors are indicated on the operation indicators.
• Errors are indicated with error codes.
9-1-1
Errors Indicated on Operation Indicators
NORM/ERR
Reader/Writer operating status
Running
Normal opera-
Run Mode
tion
Safe Mode
SLAVE Mode
Errors for
WDT error
which the
IP address conflict
Reader/Writer
will not operate
BOOTP server
connection error
Errors for
Command error
which the
RF Tag communi-
Reader/Writer
cations error
will operate
Minor fault
Major fault
Note If these errors are detected during operation, the RUN indicator will flash at 0.4-s intervals.
9 - 2
RF
RUN
Operation indicators
RUN (green)
NORM/ERR (red)
Flashing at 0.1-s
Not lit
intervals
Lit
Not lit
Flashing at 0.4-s
Not lit
intervals
Lit
Not lit
Not lit
Lit
Flashing at 0.1-s
Flashing irregu-
intervals
larly twice
Flashing at 0.1-s
Flashing irregu-
intervals
larly twice
Lit
Flashes once
Lit
Flashes once
Lit (See note.)
Flashing at 0.4-s
intervals
Lit (See note.)
Lit
LINK/ACT
NORM/ERR
NORM/ERR
NORM/ERR
Execution of RF
Tag communica-
tions
Not possible
Possible
Not possible
Not possible
Not possible
Not possible
Not possible
Possible
Possible
Not possible
Not possible
UHF RFID System V780-series Reader/Writer User's Manual (Z389)
Communications
connection to the
host device
Not possible
Possible
Possible
Not possible
Not possible
Not possible
Not possible
Possible
Possible
Possible
Possible