ActiveScale™ X100 Installation Guide
Condition (fully configured)
Power requirements
Rack units (U)
Relative humidity
System dimensions
System dimensions (without
doors)
Temperature
Temperature de-rating
Temperature gradient
Thermal output
Non-operating
N/A
2
42U
10% to 95% non-condensing
• Width—23.6 in (600 mm)
• Depth—52.6 in (1338 mm)
• Height—81.1 in (2060 mm)
• Width—23.6 in (600 mm)
• Depth—47.2 in (1200 mm)
• Height—81.1 in (2060 mm)
40°F to 158°F
(-40°C to 70°C)
33.8°F per 984.2 ft above 9842.5 ft
(1°C per 300 m above 3000 m)
86°F (30°C)/hour
N/A
12
Operating
Base configuration typical/max:
• 2.5/3.3 kW
Base +1 configuration typical/max:
3.15/3.98 kW
Base +2 configuration typical/max:
3.8/4.66 kW
Base +3 configuration typical/max:
4.45/5.34 kW
Base +4 configuration typical/max:
5.1/6.02 kW
Base +5 configuration typical/max:
5.75/6.7 kW
Full (Base +6) configuration typical/max:
6.4/7.4 kW
System Expansion Node kit:
• .195 to 0.23 kW
8% to 90% non-condensing
50°F to 95°F
(10°C to 35°C)
33.8°F per 984.2 ft above 3116.8 ft
(1°C per 300 m above 950 m)
68°F (20°C)/hour
Partial configuration (one column of
populated sleds):
• 8.53/11.26 KBTU/h
Full configuration (seven columns of
populated sleds):
• 21.83/ 25.25 KBTU/h
System Expansion Node kit:
• 0.665 to 0.785 KBTU/hour