Airflow Considerations; Pdu Connector Types; Table 2-30. Airflow Requirements - Western Digital ActiveScale X100 Installation Manual

Hide thumbs Also See for ActiveScale X100:
Table of Contents

Advertisement

ActiveScale™ X100 Installation Guide
• Cables - consider removing cables, including ramped cable covers, from the walking path before
moving the pallet. Leaving the cables in place creates a safety hazard for the installation team and can
damage the cables.
• Lift locations - there may be locations along the walking path where the system must be lifted in
order to proceed. Make sure that lift equipment is available at this location on the day of the delivery.
• Elevators - ensure that any elevators that will be required to lift the equipment to the data center/
computer room are rated to carry the full load of the system plus passengers.

2.4 Airflow considerations

Ensure that both the front and rear of the ActiveScale X100 stay clear of any materials that may block or
disrupt the airflow in any way. Disrupting the airflow can cause the system to overheat, which may affect
performance or cause damage to the system.
The following rack airflow principles should be considered for best results:
• Controlled air conditioners that are functional and can sufficiently maintain specified system
operating temperatures should be located in the facility where the system will be installed.
• The airflow in and out of the equipment must not be restricted.

Table 2-30. Airflow requirements

Condition (fully configured)
Altitude
Relative humidity
Temperature
Temperature de-rating
Temperature gradient
Thermal output

2.5 PDU connector types

This section provides information specific to the PDU connection types.
Non-operating
-984 ft to 39,3711 ft
(-300 m to 12,000 m)
10% to 95% non-condensing
40°F to 158°F
(-40°C to 70°C)
33.8°F per 984.2 ft above 9842.5 ft
(1°C per 300 m above 3000 m)
86°F (30°C)/hour
N/A
17
Operating
-984 ft to 10,000 ft
(-300 m to 3048 m)
8% to 90% non-condensing
50°F to 95°F
(10°C to 35°C)
33.8°F per 984.2 ft above 3116.8 ft
(1°C per 300 m above 950 m)
68°F (20°C)/hour
Partial configuration (one column
populated sleds):
• 8.53/11.26 KBTU/h
Full configuration (seven columns of
populated sleds):
• 21.83/ 25.25 KBTU/h
System Expansion Node kit:
• 0.665 at 0.785 KBTU/hour