System Specification Summary - Western Digital ActiveScale X100 Installation Manual

Hide thumbs Also See for ActiveScale X100:
Table of Contents

Advertisement

ActiveScale™ X100 Installation Guide
B.1 System specification summary
The following table is a summary of specifications relevant to the ActiveScale X100.
Condition (fully configured)
Altitude
Packed system dimensions
Power requirements
Rack units (U)
Relative humidity
System dimensions
System dimensions (without
doors)
Temperature
Temperature de-rating
Temperature gradient
Non-operating
-984 ft to 39,3711 ft
(-300 m to 12,000 m)
• Width—41.4 in (1052 mm)
• Depth—61.41 in (1560 mm)
• Height—88.3 in (2243 mm)
N/A
2
42U
10% to 95% non-condensing
• Width—23.6 in (600 mm)
• Depth—52.6 in (1338 mm)
• Height—81.1 in (2060 mm)
• Width—23.6 in (600 mm)
• Depth—47.2 in (1200 mm)
• Height—81.1 in (2060 mm)
40°F to 158°F
(-40°C to 70°C)
33.8°F per 984.2 ft above 9842.5 ft
(1°C per 300 m above 3000 m)
86°F (30°C)/hour
143
Operating
-984 ft to 10,000 ft
(-300 m to 3048 m)
Base configuration typical/max:
• 2.5/3.3 kW
Base +1 configuration typical/max:
3.15/3.98 kW
Base +2 configuration typical/max:
3.8/4.66 kW
Base +3 configuration typical/max:
4.45/5.34 kW
Base +4 configuration typical/max:
5.1/6.02 kW
Base +5 configuration typical/max:
5.75/6.7 kW
Full (Base +6) configuration typical/max:
6.4/7.4 kW
System Expansion Node kit:
• .195 to 0.23 kW
8% to 90% non-condensing
50°F to 95°F
(10°C to 35°C)
33.8°F per 984.2 ft above 3116.8 ft
(1°C per 300 m above 950 m)
68°F (20°C)/hour
1

Advertisement

Table of Contents
loading

Table of Contents