Install Rectifier Modules And Battery Interface Unit - Avaya S8700 Installing

With avaya mcc1 or scc1 media gateways
Hide thumbs Also See for S8700:
Table of Contents

Advertisement

84
Installing the Avaya™ S8700 Media Server with Avaya™ MCC1 or SCC1 Media Gateway

Install Rectifier Modules and Battery Interface Unit

Each rectifier module operates as an integral part of a complete power system with battery
backup. The modules operate in a redundant, high reliability mode to provide -48 VDC at 850
W to a common power bus.
The Battery Interface Unit controls the rectifier modules, manages the batteries, and reports the
status of system power. The unit provides the Remote Power Off (RPO) option and battery
alarm interfaces for internal and external alarms.
Install the BU3200A Battery Interface Unit (comcode 107781502) in the first slot of the
1
power distribution unit. See
NOTE:
The Battery Interface Unit and the rectifier modules are keyed and can only install 1 way.
Install the first 2 RM0850HA100 Rectifier Modules (comcode 107793796) into the
2
second and third slots of the power distribution unit.
If 2 to 3 carriers are installed in the system, install a third rectifier module (N+1).
3
4
If 4 to 5 carriers are installed in the system, install a fourth rectifier module.
The fifth rectifier module slot is reserved for future system growth.
5
Rectifier Module Installation
Figure notes
1
2
3
Install Battery Interface Unit into Slot 1
Install Rectifier Modules into Slots 2-5
Rectifier Module 3 (in Slot 4)
''Rectifier Module Installation'' on page
4
5
May 2003
84.
Test Points
Main Circuit Breakers

Advertisement

Table of Contents
loading

Table of Contents