Check Commercial Power And Connect Ac Power - Avaya S8700 Installing

With avaya mcc1 or scc1 media gateways
Hide thumbs Also See for S8700:
Table of Contents

Advertisement

Installing the Avaya™ S8700 Media Server with Avaya™ MCC1 or SCC1 Media Gateway

Check Commercial Power and Connect AC Power

Before powering up the media gateways, check the AC power using a KS-20599 digital
voltmeter (DVM) (or equivalent).
1
Set the DVM to the 250 volt range.
Carefully measure the voltage between the hot and neutral side of the receptacle. The
2
neutral wire is white, the hot wire is black.
Verify the meter reads 106 to 128 VAC. If not, have a qualified electrician correct the
3
problem.
Measure the voltage between the neutral and ground side of the receptacle. The ground
4
wire is green.
5
Verify the meter reads 0 VAC. If not, have a qualified electrician correct the problem.
Set all media gateway power modules
6
. Plug the AC power cable into the receptacle.
OFF
May 2003