Set The Clock Options - Avaya S8700 Installing

With avaya mcc1 or scc1 media gateways
Hide thumbs Also See for S8700:
Table of Contents

Advertisement

Installing the Avaya™ S8700 Media Server with Avaya™ MCC1 or SCC1 Media Gateway
At the clock cabinet, connect a 6 AWG (#40) (16 mm
3
the terminal strip.
Route the wires out of the cabinet and to the DC power plant.
4
At the DC power plant, connect the -48V wire to the DC OUTPUT circuit breaker.
5
6
At the DC power plant, connect the -48VRTN wire to the DISCH GRD bar.

Set the Clock Options

There are four sets of option switches on the clock.
1
Set the options on the Clock Input (CI) circuit pack according to
Settings'' on page
Set the options on the Stratum 3 Clock (ST3) circuit pack according to
2
Circuit Pack Option Switch Settings'' on page
Set the options on the Composite Clock Timing Output (TOCA) circuit pack according
3
to
''Composite Clock Timing Output (TOCA) Circuit Pack'' on page
Set the Stratum 2/Stratum 3 switch to the STRATUM 3 position.
4
CI Option Switch Settings
Switch
Function
1
T1 Select
2
CC Select
3
Framing Select
4
BX.25
ST3 Clock Circuit Pack Option Switch Settings
Switch
Status/Results
SW1
OFF = minor alarm never output
Minor
Alarm
ON = minor alarm is output if holdover occurs
Control
SW2
OFF = major alarm is output and fail lamp lights if 5 VDC
Major
power is lost and 4 kHz output is lost
Alarm
Control
ON = major alarm is output and fail lamp lights if 5 VDC
power is lost and 4 kHz output is lost and holdover occurs
179.
Position
OFF = enable (default)
ON = disable
OFF = enable
ON = disable (default)
OFF = ESF
ON = D4 (default)
OFF = enable
ON = disable (default)
May 2003
Installing the Stratum 3 clock (if used)
2
) wire to the -48VRTN terminal on
''CI Option Switch
''ST3 Clock
179.
180.
179