Connect Ground For Dc Power Cabinet; Connect Dc Battery Frame Ground - Avaya S8700 Installing

With avaya mcc1 or scc1 media gateways
Hide thumbs Also See for S8700:
Table of Contents

Advertisement

104
Installing the Avaya™ S8700 Media Server with Avaya™ MCC1 or SCC1 Media Gateway
NOTE:
The ground plates and cabinet clips are installed later in this procedure.
Connect Ground to DC power cabinet
''Connect Ground for DC power cabinet'' on page 104
''Connect DC Power Distribution Unit Ground'' on page 105
''Connect DC Power Cabinet Ground'' on page 106

Connect Ground for DC power cabinet

1
At the DC power cabinet, connect a 1 AWG (#70) (7 mm
DISCHARGE bar. See
2
Route the ground wire out of the cabinet and terminate it on the approved ground.
!
CAUTION:
The approved ground must be connected using the correct gauge wire, terminated with a
listed clamp, and identified with a grounding tag (FORM 15657NR, or equivalent).
Grounding for DC power cabinet
Figure notes
1
2

Connect DC Battery Frame Ground

Cut a length of 6 AWG (#40) (4 mm
1
cabinet and the DC battery cabinet. See
Battery Cabinet'' on page
Crimp a terminal lug on the each end of the wire. The terminal lugs are furnished as part
2
of D-181895, kit of parts.
''Grounding for DC power cabinet'' on page
3
2
DC power cabinet
To Approved Ground
1
dc_rect1 RBP 051396
1 AWG (#70) (7 mm
3
4
Ground Discharge Bar
2
) wire long enough to reach between the DC power
''Frame Ground Wiring Between cabinet and
105.
May 2003
2
) ground wire to the GROUND
104.
4
2
) Wire