Connect Dc Power Distribution Unit Ground - Avaya S8700 Installing

With avaya mcc1 or scc1 media gateways
Hide thumbs Also See for S8700:
Table of Contents

Advertisement

Installing the Avaya™ S8700 Media Server with Avaya™ MCC1 or SCC1 Media Gateway
At the DC battery cabinet, attach the 6 AWG (#2540) (6 4 mm
3
ground mounting hole using a pan head slotted screw, star washer, and hex nut. Tighten
the screw securely.
4
Route the opposite end of the wire to the DC power cabinet.
5
Attach the 6 AWG (#40) (4 mm
a pan head slotted screw, star washer, and hex nut. Tighten the screw securely.
Frame Ground Wiring Between cabinet and Battery Cabinet
3
Figure notes
1
6 AWG (#40) (4mm
DC Battery Cabinet
2
3
DC power cabinet
4
Grounding Hole in Top of cabinet

Connect DC Power Distribution Unit Ground

Measure and cut a length of 6 AWG (#40) (4 mm
1
the GROUND DISCHARGE bar in the DC power cabinet and the GRD connector on the
DC-powered Distribution Unit. See
page
106.
At the cabinet, connect a the 6 AWG (#40) (16 4 mm
2
DISCHARGE bar.
2
) wire to the mounting hole in the top of the cabinet. Use
1
2
) Wire
5
Terminal Lug (Part of D-18181895)
Pan Head Slotted Screw
6
7
Star Washer
8
Hex Nut
''Ground for the DC-Powered Distribution Unit'' on
May 2003
2
) wire to the frame
2
dc_rect6 RBP 052996
2
) wire long enough to reach between
2
) wire to the GROUND
105