Migrating to an Avaya™ S8700 Media Server with Avaya™ MCC1 or SCC1 Media Gateway
Configure the SNMP Modules in the UPSs
Setting selected traps (alarming)
The default is to set all traps, which may result in large log entries. Therefore, only set the
following traps. Refer to the User's Guide that comes with the SNMP module for the menus and
commands for setting these traps.
•
UPS on Battery—Indicates AC fail with pending shutdown based on battery reserve
available
•
UPS in Bypass—Failure either Failed UPS or overload
•
Replace battery—Failure of periodic (28day) battery test indicating battery needs to be
replaced.