Install The Mcc1 Cabinets; Install Emergency Transfer Ground Wire; Remove The Present System; Unpack And Install The Cabinet - Avaya DEFINITY Server R Manual

Upgrades and additions
Hide thumbs Also See for DEFINITY Server R:
Table of Contents

Advertisement

Upgrading G3vs to an Avaya DEFINITY Server R
running Avaya MultiVantage Software

Install Emergency Transfer Ground Wire

!
CAUTION:
To avoid contaminating single-point ground, do not connect the ground strap
while the system is powered up.
1. Connect a 10 AWG (#25) (2.6 mm
block or to pin 49 of the CAP (cable access panel) associated with the
emergency transfer panel.
2. Route the other end of the wire to an approved ground and connect.
Disconnect Power and Ground
1. Disconnect the cabinet power cords from the rear of the cabinet.
2. Disconnect the 10 AWG (#25) (2.6 mm
3. Disconnect the 6 AWG (#40) (4.1 mm
ground bar in the cabinet.

Remove the Present System

1. Disconnect the management terminal from the TERM connector.
2. Remove all of the 25-pair cables from the rear of the system. Retain any
cables that can be reused with the new cabinet.
3. Remove the AC power cord from the system.
4. Remove the ground wires from the system. If the wires can reach the new
cabinet, save them.

Install the MCC1 Cabinets

Unpack and Install the Cabinet

1. Refer to the MCC1 installation instructions (http://made-easy.avaya.com/).
!
2. Return to this section when the installation of the MCC1 is completed.
3-14
Issue 5 October 2002
CAUTION:
Do not power up the system.
2
) wire either to pin 49 of the connecting
2
) coupled bonding conductor wire.
2
) CABINET GROUND wire from the
555-233-115

Advertisement

Table of Contents
loading

Table of Contents