Siemens Sinumerik 840D sl Function Manual page 733

Sinumerik safety integrated
Hide thumbs Also See for Sinumerik 840D sl:
Table of Contents

Advertisement

10/15
27306
Parameter
Explanation
Response
Remedy
Program
r
continuation
27350
Parameter
Explanation
© Siemens AG 2015 All Rights Reserved
SINUMERIK 840D sl/SINAMICS S120 SINUMERIK Safety Integrated (FBSI sl) - - 10.2015 Edition
F_DP: Max. number of active SPL connections (%1) for (%2)
exceeded
%1 = maximum number of possible SPL connections
%2 = communication type
In the active parameterizing data sets for the specified communication
type (F_SENDDP/FRECVDP), more than the permissible number of
SPL connections, designated using different IDs (MD13331/13341
$MN_SAFE_SDP/RDP_ID), were parameterized.
Alarm display
NC start disable in this channel
Interface signals are set
Mode group not ready
Channel not ready
Correct the identifiers of the active SPL connections or deactivate the
SPL connections (MD13330/13340 $MN_SAFE_SDP/RDP_ENA-
BLE_MASK).
Set the option for an extended number of connections.
Switch--off – switch--on the control
F_DP: %1 communication, connection %2 signals error %3
%1 = communication type
%2 = name or DP_DP_ID of the communication relationship
%3 = error detection
There is an F_DP communication error with the external communica-
tion partners and the programmed error response is
$A_FSDP_/FRDP_ERR_REAC = 0 or 1.
The following displays are possible for communication type (%1):
-- F_SENDDP
-- F_RECVDP
As connection (%2), the name of the DP_DP_ID (ID) or the SPL
connection is displayed.
One of the following error causes is possible (see fault ID %3):
-- SN: An error was detected in the telegram sequence.
-- CRC: A CRC error was detected.
-- TO: The parameterized communication timeout has been exceeded.
All of the specified error IDs, depending on the error profile, can also be
displayed in a combination.
10.2NCK safety alarms for Sinumerik 840D sl
Diagnostics
10-733