Data Description
8.2 Parameters for SINAMICS S120
p9516
SI Motion, encoder configuration, safety- -related functions (CU)
Sets the configuration for encoder and position actual value.
The encoder, which is used for safe motion monitoring on the Control Unit must
be parameterized in this parameter.
Bit 00: Encoder, rotary/linear
1 signal: Linear, 0 signal: Rotary
Bit 01: Actual position value, sign change
1 signal: Yes, 0 signal: No
Bit 04: STOP A after encoder fault for 1- -encoder safety
1 signal: no, 0 signal: Yes
See also: p0404, p0410 and F01671
The following applies to safety- -related functions that have not been enabled
(p9501 = 0):
- - p9516.0 is automatically set the same as p0404.0 when the system boots.
- - p9516.1 is automatically set the same as p0410.1 when the system boots.
The following applies for enabled safety- -related functions (p9501 > 0):
- - p9516.0 is checked to ensure that it matches p0404.0.
Unit:
Default value:
- -
0
The information whether a 1--encoder system or 2--encoder system is not included
in this parameter. This is derived from the parameter p9526 "SI Motion encoder
assignment control".
p9517
SI Motion linear scale grid division (Control Unit)
Sets the grid division for a linear encoder
The encoder, which is used for safe motion monitoring on the Control Unit must
be parameterized in this parameter.
See also: p0407, p9516 and F01671
The following applies to safety- -related functions that have not been enabled
(p9501 = 0):
- - when booting p9517 is automatically set the same as p0407.
The following applies for enabled safety- -related functions (p9501 > 0):
- - p9517 is checked to ensure that it coincides with p0407.
Unit:
Default value:
nm
10 000
p9518
SI Motion encoder pulses per revolution (Control Unit)
Sets the number of encoder pulses per revolution for rotary motor encoders.
The encoder, which is used for safe motion monitoring on the Control Unit must
be parameterized in this parameter.
See also: p0418 and F01671
The following applies to safety- -related functions that have not been enabled
(p9501 = 0): p9518 is automatically set the same as p0408 during booting.
The following applies for enabled safety- -related functions (p9501 > 0): p9518 is
checked to ensure that it coincides with p0408.
Unit:
Default value:
2048
8-444
SINUMERIK 840D sl/SINAMICS S120 SINUMERIK Safety Integrated (FBSI sl) - - 10.2015 Edition
Minimum value:
Maximum value:
- -
- -
Minimum value:
Maximum value:
0
250 000 000
Minimum value:
Maximum value:
0
16777215
Checksum:
Protection level:
Yes
3
Data type:
Effective:
Unsigned16
POWER ON
Checksum:
Protection level:
Yes
3
Data type:
Effective:
Floating Point32
POWER ON
Checksum:
Protection level:
Yes
3
Data type:
Effective:
Unsigned32
POWER ON
© Siemens AG 2015 All Rights Reserved
10/15