Siemens Sinumerik 840D sl Function Manual page 567

Sinumerik safety integrated
Hide thumbs Also See for Sinumerik 840D sl:
Table of Contents

Advertisement

10/15
Step 7:
Issue a user agreement (see Chapter 5.4.4, "User agreement")
S The safe limit positions and safe cams are now activated (provided that they
have been enabled, refer to Chapter 5.5, "Enabling safety--related functions").
This step can be omitted if you do not wish to use either of these functions.
S The key--operated switch must be set to position 3 in order to issue a user
agreement.
Step 8:
Carry out the acceptance test and enter in the logbook.
S All of the safety functions that have been enabled must be tested. For sugges-
tions on how to test activated SI functions, please refer to Chapter 9.5.2,
"Acceptance test" and/or 9.5 "Acceptance report".
S The parameterization of all PROFIsafe I/O components should be checked
using a function test and checking the printout of the hardware configuration
from SIMATIC Step 7.
Step 9:
S Save all machine data using the "Services" area. This data can be used to
commission series equipment.
S Save (back--up) the complete SIMATIC Step7 project.
Warning
!
After the acceptance test has been completed, all illegal (old) MD files must be
removed from the Flashcard (to avoid confusion between old and new data).
Data that corresponds to the acceptance test data must be backed--up (archived).
Step 10:
Delete (clear) the password in order to prevent the unauthorized change of
machine data.
© Siemens AG 2015 All Rights Reserved
SINUMERIK 840D sl/SINAMICS S120 SINUMERIK Safety Integrated (FBSI sl) - - 10.2015 Edition
9.2 Procedure when commissioning the drive for the first time
Commissioning