Siemens Sinumerik 840D sl Function Manual page 209

Sinumerik safety integrated
Hide thumbs Also See for Sinumerik 840D sl:
Table of Contents

Advertisement

10/15
Configuration
The F I/O are configured while configuring the standard I/O bus configuration using
STEP 7.
Parameterization
Both the standard and F parameterization of the F modules is carried out using the
relevant properties dialog box of the module. Select the appropriate I/O device
(e.g. IM 151--1) in the station window and then open the properties dialog box of
the relevant F module in the detailed view.
Note
The parameter assignments specified in this chapter only refer to the ET 200
modules.
Parameters: Input/output address
The following conditions apply to the input/output addresses of an F module:
S Input address for PLC317 PN PLC 317F
S Output address = input address
F parameterization
F parameterization is realized in the properties dialog box under:
Dialog: Properties
Tab: Parameter
Parameters > F parameters
The F parameters of the PROFIsafe components are automatically set to the
F monitoring time of the HW Config and cannot be changed.
The displayed values of the F parameters
S F_source_address
S F_target_address
must be entered into the machine data to parameterize the NCK in a subsequent
parameterizing step.
The value of the F target addresses should be set at to the I/O module (F module)
using the DIL switches provided.
© Siemens AG 2015 All Rights Reserved
SINUMERIK 840D sl/SINAMICS S120 SINUMERIK Safety Integrated (FBSI sl) - - 10.2015 Edition
Connecting Sensors/Actuators
7.2 Connecting I/O via PROFIsafe
7-209