8 Applied Settings
8-9

Applied Output

8-9-1

Analog Disconnection Signal

Assign the output terminal functions 050 [Ai1Dc], 051 [Ai2Dc], and 052 [Ai3Dc] analog break signals to
one of [CC-01] to [CC-17] that corresponds to the output terminal and output the signals.
The signals will be output when the input values of the analog inputs [Ai1], [Ai2], and [Ai3] are within the
range from the lower limit level to the upper limit level of the window comparators. The analog inputs
can be monitored at any value, so that this function can be used for detecting breaks, for example.
A hysteresis width can be specified to the upper and lower limit levels of the window comparator.
A level and a hysteresis width can be specified to each of the analog inputs [Ai1], [Ai2], and [Ai3] indi-
vidually.
Precautions for Correct Use
• When the signal [WCAi1], [WCAi2], or [WCAi3] is output, the value adopted to the analog
input can be fixed to any value. Specify the value using the break operation level [Ai1], [Ai2],
or [Ai3].
• When the analog hold function [AHD] is enabled, the input being held has higher priority.
 Parameter
Item
Output terminal func-
tion selection 11-15
Relay output terminal
function selection
16A-16C
Relay output terminal
function selection
AL1-AL0/AL2-AL0
Output terminal func-
tion selection 11-15
Relay output terminal
function selection
16A-16C
Relay output terminal
function selection
AL1-AL0/AL2-AL0
Window comparator
Ai1/Ai2/Ai3 upper limit
level
Window comparator
Ai1/Ai2/Ai3 lower limit
level
Window comparator
Ai1/Ai2/Ai3 hysteresis
width
Ai1/Ai2/Ai3 abnormal
condition analog oper-
ation level
8 - 148
Parameter
Data
[CC-01] to
[CC-05]
050
[CC-06]
051
052
[CC-07]
[CC-01] to
[CC-05]
056
[CC-06]
057
058
[CC-07]
Ai1:[CE-40]
0 to 100(%)
Ai2:[CE-43]
Ai3:[CE-46]
-100 to 100(%)
Ai1:[CE-41]
0 to 100(%)
Ai2:[CE-44]
Ai3:[CE-47]
-100 to 100(%)
Ai1:[CE-42]
Ai2:[CE-45]
0 to 10(%)
Ai3:[CE-48]
Ai1:[CE-50]
0 to 100(%)
Ai2:[CE-52]
Ai3:[CE-54]
-100 to 100(%)
High-function General-purpose Inverter RX2 Series User's Manual
Description
The signals 050 [Ai1Dc], 051 [Ai2Dc], and 052
[Ai3Dc] will be output to the output terminal assigned.
The signals 056 [WCAi1], 057 [WCAi2], and 058
[WCAi3] will be output to the output terminal
assigned.
Specify the upper limits of the analog inputs. The set-
ting ranges are limited to the lower limits or greater.
Specify the lower limits of the analog inputs. The set-
ting ranges are limited to the upper limits or smaller.
The maxim hysteresis widths are limited to (upper
limit level - lower limit level)/2.
Specify the input values when the input become
within the ranges according to their operation level
selection.