(Ex.3) When [bb-20] ≠00 and [bb-24] = 01, it restarts by picking up the frequency.
Control Power Supply
Inverter
Output
Motor Speed
Output signal
[AL]
Note The motor will trip after instantaneous power failure allowable time.
See 7-5-3 Frequency Matching Start on page 7-65 for details.
(Ex.4) When [bb-20] ≠00 and [bb-24] = 02, it restarts with frequency pull-in.
Control Power Supply
Inverter
Output
Motor Speed
Output signal
[AL]
Note The motor will trip after instantaneous power failure allowable time.
See 7-5-4 Frequency Pull-in Start on page 7-69 for details.
(Ex.5) When [bb-20] ≠00 and [bb-24] = 03, it restarts using the motor speed feedback.
Control Power Supply
Inverter
Output
Motor Speed
Output signal
[AL]
Note The motor will trip after instantaneous power failure allowable time.
For motor speed feedback, the feedback input to the input terminals A and B, or feedback input to the
optional cassette PG option unit is required.
High-function General-purpose Inverter RX2 Series User's Manual
Instantaneous power
failure allowable time
Free Running
Retry Standby
Time
Instantaneous power
failure allowable time
Free Running
Retry Standby
Time
Instantaneous power
failure allowable time
Free Running
Retry Standby
Time
8 Applied Settings
8 - 57
8