9 Communications Functions
*2. The management inverter sends the master switching command from Inverter No. 01 to 02 after data is sent
from Inverter 01 (master) to a slave (or slaves), with a wait time of "silent interval  Communication Wait Time.
*3. After receiving data from the master inverter, the management inverter sends the next master switching com-
mand with a wait time of "silent interval  Communication Wait Time. If the management inverter cannnot
receive the data sent from the master inverter within the Communication Error Timeout Time, a communica-
tion timeout occurs and the management inverter follows the operation set in the Operation Selection on
Communication Error.
*4. Be sure to enable the Communication Error Timeout Time setting (= 0.01 to 99.99) on the management
inverter. When this setting is disabled (= 0), the co-inverter communication will stop if the management
inverter cannot receive data from the master. In this case, cycle the power supply for the management
inverter, or reset the management inverter (by turning ON/OFF the terminal RS).
9-6-1

Inter-inverter Communication Parameters

The parameters required to establish Inter-inverter communication are shown in the table below.
Parameter No.
*2
CF-02
*5
CF-05
CF-06
CF-07
*2
CF-08
*2
CF-20
*2
CF-21
*2
CF-22
CF-23
CF-24
CF-25
9 - 98
Function name
Communication
1 to 247
Station No. Selection
00:
01:
Operation Selection on
02:
Communication Error
03:
04:
Communication Error
0.00:
Timeout Time
0.01 to 99.99
Communication Wait
0 to 1000
Time
00:
Communication Selec-
01:
tion
02:
1 to 8
EzCom Communica-
tion Starting Station
Setting required only for manage-
Number
ment inverter
1 to 8
EzCom Communica-
tion Ending Station
Setting required only for manage-
Number
ment inverter
00:
EzCom Communica-
tion Start Selection
01:
Number of Sent Data
of All Stations in
1 to 5
EzCom Communica-
tion
Recipient Station
Number of All Stations
1 to 247
in EzCom Communi-
cation 1
Recipient Register of
All Stations in EzCom
0000 to FFFF
Communication 1
Data
*3
Trip
Trip after deceleration stop
Ignore
Free-run stop
Deceleration stop
Timeout disabled
Modbus communication
EzCom communication
EzCom communication
(management inverter)
*6
*6
*7
Start via input terminal
*8
Constant communication
*9
High-function General-purpose Inverter RX2 Series User's Manual
Setting
Default
Unit
data
target
*4
1
ALL
02
ALL
0.00
s
ALL
0
ms
ALL
B
00
A
1
A
1
A
A
00
A
5
M
1
M
0
M
*1