8 Applied Settings
 Parameter
Item
Deceleration-stop at
power failure
Decel-stop at power
failure starting voltage
Decel-stop at power
failure control target
level
Decel-stop at power
failure deceleration
time
Decel-stop at power
failure freq. width at
deceleration start
Decel-stop at power
failure DC-bus voltage
constant control
P-gain
Decel-stop at power
failure DC-bus voltage
constant control I-gain
Output terminal func-
tion
8 - 64
Parameter
Data
00
01
02
[bA-30]
03
(200 V class)
0.0 to 410.0(v)
[bA-31]
(400 V class)
0.0 to 820.0(v)
(200 V class)
0.0 to 410.0(v)
[bA-32]
(400 V class)
0.0 to 820.0(v)
0.01 to
[bA-34]
3600.00(s)
0.00 to
[bA-36]
10.00(Hz)
[bA-37]
0.00 to 5.00
0.00 to
[bA-38]
150.00(s)
[CC-01] to
023
[CC-07]
High-function General-purpose Inverter RX2 Series User's Manual
Description
Disabled
Decelerates and stops, and maintains the
stop status.
Decelerates and stops with constant DC
voltage control, and maintains the stop sta-
tus.
Decelerates and stops with constant DC
voltage control, and maintains the stop sta-
tus. If the power supply recovers during the
process, the operation continues.
This is the voltage level at which the instan-
taneous power failure non-stop control starts
when the internal power supply voltage
drops.
Switches the deceleration temporarily to
constant speed operation when the internal
power supply voltage increases due to
deceleration.
Deceleration time setting for instantaneous
power failure non-stop deceleration and stop
operation.
The setting for starting deceleration by low-
ering frequency during instantaneous power
failure non-stop deceleration and stop oper-
ation.
Proportional gain for PI control during con-
stant DC voltage control.
Integral gain for PI control during constant
DC voltage control.
[IPS] Outputs the signal during instanta-
neous power failure non-stop deceleration.
OFF: The function is not active.
ON: Instantaneous power failure non-stop
deceleration in function.
Default
data
00
(200V
class)
220.0
(400V
class)
440.0
(200V
class)
360.0
(400V
class)
720.0
1.00
0.00
0.20
1.00
-