8 Applied Settings
 Parameter
Item
Output on-delay time
Output off-delay time
(Ex.) Operation of Output terminal 11
Output of
selected function
Operation of
Output terminal 11

8-11-4 Analog Output Terminal Adjustment

You can select, using some parameter codes, data to be output to the Analog output Ao1-L and Ao2-L
terminals and the Digital pulse output FM-CM1 terminal.
Selectable Parameter Codes
The below table shows selectable parameter codes.
The output scale ranges are specified when bias settings are each set to 0.0%, and gain settings are
each set to 100.0%.
You can adjust the output scale ranges with bias settings and gain settings.
Using the bias function, you can output, from data that can output "(±) data," "(-) data" in a range from
which outputting is available.
When selecting the output monitor, set the registered number of each code. For example, when using
dA-02 of output current monitor via [Ao1] terminal, set "10002(2712h)" to Cd-04.
Code
dA-01
Output frequency monitor
dA-02
Output current monitor
dA-04
Frequency command
dA-08
Detected speed value monitor
Output frequency monitor (with
dA-12
sign)
dA-14
Frequency upper limit monitor
dA-15
Torque command monitor
dA-16
Torque limit monitor
dA-17
Output torque monitor
8 - 178
Parameter
[CC-20]/[CC-22]/[CC-24]/
[CC-26]/[CC-28]/[CC-30]/
[CC-32]
[CC-21]/[CC-23]/[CC-25]/
[CC-27]/[CC-29]/[CC-31]/
[CC-33]
ON
OFF
ON
OFF
[CC-20]
Name
Data
0.00 to 100.00(s)
Sets an on-delay time.
0.00 to 100.00(s)
Sets an off-delay time.
[CC-21]
Output scale range
(Corresponding to 0 to 10 V /
0 to 20 mA / 0 to 100%)
0.00 to Maximum speed (Hz)
(0.00 to 2.00) ×
Inverter rated current (A)
0.00 to Maximum speed (Hz)
0.00 to Maximum speed (Hz)
0.00 to Maximum speed (Hz)
0.00 to Maximum speed (Hz)
0 to Motor rated torque ×
*1
500% (Nm)
0 to Motor rated torque ×
*1
500% (Nm)
0 to Motor rated torque ×
*1
500% (Nm)
High-function General-purpose Inverter RX2 Series User's Manual
Description
Remarks
Outputting is possible with (±).
Outputting is possible with (±).
Outputting is possible with (±).
Outputting is possible with (±).
Outputting is possible with (±).
Outputting is possible with (±).