6 Basic Parameter Settings
An example of operation on [FUP] and [FDN] terminals is shown as follow:
Operation command.
(FW,RV)
FUP
FDN
Frequency command
Output frequency
 Parameter
Item
Main speed input
source selection,
1st-motor
Input terminal function
selection
FUP/FDN overwriting
target selection
FUP/FDN data save
enable
FUP/FDN UDC
selection
Acceleration time set-
ting for FUP/FDN func-
tion
Deceleration time set-
ting for FUP/FDN func-
tion
*1. Default data when default data selection (UB-02) is set to 01.

6-4-12 Analog Command Hold Function (AHD)

The input terminal 019 [AHD] analog command holding holds the command of the analog input when
the input terminal becomes ON. When the input terminal becomes OFF, the command returns to the
analog command.
If the main speed command [AA101] is an analog input command (01-03), this function is effective even
when data are held by the analog command holding [AHD] function.
If 019[AHD] function is effective, the held data can be moved up/down by using [FUP]/[FDN] function.
Precautions for Correct Use
Data changes with the [FUP]/[FDN] function are not saved.
6 - 42
ON
ON
ON
Parameters
Data
[AA101]
01 to 15
020
[CA-01] to
021
[CA-11]
022
00
[CA-60]
01
00
[CA-61]
01
00
[CA-62]
01
0.00 to
[CA-64]
3600.00(s)
0.00 to
[CA-66]
3600.00(s)
High-function General-purpose Inverter RX2 Series User's Manual
ON
If [FUP] and [FDN] terminals are made ON simul-
taneously, acceleration/deceleration is not made.
Description
01: Ai1-L input, 02: Ai2-L input, 03: Ai3-L input,
07: parameter setting,
08: RS485 communication,
12: pulse string input (main body),
14: program function, 15: PID arithmetic
FUP: Acceleration through remote operation
FDN: Deceleration through remote operation
UDC: Clearing of remote operation data
Overwrites the frequency command.
PID target value is overwritten.
The command is not saved in case of power
shutdown.
The command is saved in case of power shut-
down.
Cleared to 0 Hz.
Cleared to the saved command.
Sets acceleration time for FUP/FDN functions.
Sets deceleration time for FUP/FDN functions.
Default
data
*1
01
-
00
00
00
30.00
30.00