Example: [E001] occurred when the current reached the overcurrent level.
[bb160] Overcurrent level
Output current
Output frequency
Output signal [AL]
8-6-2

Fatal Fault Signal (MJA)

The following table shows signals that are output when any of trips occurs. It is different form the Output
signal 017 (AL) that will be output for all trips.
This signal converts the trips caused by a hardware failure.
Trips that are evaluated as serious faults are as follows.
Precautions for Correct Use
The inverter hardware may have a fault when this signal is output. Check the error history and
deal with the situation appropriately.
Error code
E008
E010
E011
E014
E019
E020
 Parameter
Item
Output terminal func-
tion selection 11-15
Relay output terminal
function selection
16A-16C
Relay output terminal
function selection
AL1-AL0/AL2-AL0
High-function General-purpose Inverter RX2 Series User's Manual
Name
The memory element of the inverter is under an abnormal condi-
Memory element error
tion.
The current detector of the inverter is under an abnormal condi-
Current detector error
tion.
CPU error
The drive CPU of the inverter is under an abnormal condition.
Ground fault error
The inverter has a ground fault.
Temperature detector
The temperature detector of the inverter is under an abnormal
error
condition.
Cooling fan rotation
The cooling fan rotation speed of the inverter has reduced, pre-
speed reduction error
venting the inverter from dissipating heat.
Parameter
Data
[CC-01] to
[CC-05]
[CC-06]
018
[CC-07]
8 Applied Settings
Description
Description
The signal will be output when a serious fault error
occurs in the output terminal to which 018 [AL] has
been assigned.
OFF: No serious fault has occurred.
ON: A serious fault has occurred.
8
8 - 125