[Cd-01] [FM] Terminal Output Form Selection is Set to 01
With the "Bias adjustment [Cd-13]" of the "Digital frequency output," you can bias Point 0 as shown in
the below figure.
Digital frequency (Hz)
[Cd-02]
[Cd-02]/2
[Cd-13]=0.0(%)
-[Cd-02]/2
(Ex.) Digital-frequency-outputting information on [dA-01] output frequency monitor
Output so that the maximum values of the digital frequency output corresponds to the maximum fre-
quency.
When the maximum frequency is 60 Hz, set [Cd-02]=60Hz.
[Cd-13]=0.0%, [Cd-14]=100.0%
Digital frequency (Hz)
60Hz
30Hz
0
0Hz
With the "Gain adjustment [Cd-14]" of the "Digital frequency output," you can change an inclination as
shown in the below figure.
Digital
frequency (Hz)
[Cd-02]
[Cd-02]/2
0
0
-[Cd-02]/2
High-function General-purpose Inverter RX2 Series User's Manual
[Cd-13]=50.0(%)
Parallel
movement
0
0
Maximum
[Cd-13]= -50.0(%)
Output frequency (Hz)
30Hz
Maximum frequency
60Hz
[Cd-14]=200.0(%)
[Cd-14]=100.0(%)
Change in
[Cd-14]=50.0(%)
inclination
Outputting will
be made in this
range.
Maximum
Full scale (FS)
[Cd-14]= -50.0(%)
Outputting will
be made in this
range.
Output scale
8 Applied Settings