Connection of PID1 with PID2
Setting the target value of PID2 to PID1 output ([AJ-07] = 15) enables double-layer control of PID.
(PID3/PID4 cannot be selected.)
Enable PID2 output command as follows.
PID1 control
PID2 control
PID3 control
PID4 control
PID2 is enabled
Parameter
Item
PID2 enable
PID2 deviation inverse
Input source selection
of Set-point for PID2
Set-point setting for
PID2
Input source selection
of Process data for
PID2
PID2 proportional gain
PID2 integral time con-
stant
High-function General-purpose Inverter RX2 Series User's Manual
PID output switch
[PIO1]/[PIO2]
[db-50]
command
[db-55]
[db-57]
[db-59]
Combination of PIO1/PIO2
[PIO2]
Parameter
Data
00
01
[AJ-01]
02
00
[AJ-02]
01
[AJ-07]
00 to 15
0.00 to
[AJ-10]
*1
100.00(%)
[AJ-12]
00 to 13
[AJ-13]
0.0 to 100.0
[AJ-14]
0.0 to 3600.0(s) Integral gain
PID
Output
OFF
Description
Disable
Enable (if command becomes negative, it
does not output in a reverse direction)
Enable (if command becomes negative, it
outputs in a reverse direction)
Disable
Enabled (polarity inversion of deviation)
00: Disable, 01: Ai1-L input, 02: Ai2-L input,
03: Ai3-L input, 04: (Reserved),
05: (Reserved), 06: (Reserved),
07: Parameter setting [AH-44],
08: RS 485 communication, 09: Option 1,
10: Option 2, 11: Option 3,
12: Pulse train input (main unit),
13: Pulse train input (option),
15: PID1 output
Is a parameter set value.
00: Disable, 01: Ai1-L input, 02: Ai2-L input,
03: Ai3-L input, 04: (Reserved),
05: (Reserved), 06: (Reserved),
07: Parameter setting [AH-44],
08: RS 485 communication, 09: P option 1,
10: Option 2, 11: Option 3,
12: Pulse train input (main unit),
13:Pulse train input (option)
Proportional gain
8 Applied Settings
[PIO1]
ON
Default
data
00
00
07
0.00
02
0.1
0.1
8 - 27
8