5-12 Braking Resistor Load Ratio Monitor
Display the use rate of braking resistor circuit (BRD).
Precautions for Correct Use
• A setting is required for a braking resistor circuit (BRD) to operate.
For details, see 8-2-5 Regenerative Braking Function on page 8-50.
• The breaking resistor overload error [E006] is generated when the displayed rate exceeds
the Dynamic brake usage rate [bA-60].
Parameter
Item
BRD load factor monitor
Dynamic brake usage rate
High-function General-purpose Inverter RX2 Series User's Manual
Parameter
Data
[dA-41]
0.00 to 100.00 (%)
[bA-60]
0.0 to 100.0 (%)
5 Monitor
Description
Displays the load ratio of braking resis-
tor.
Sets the maximum use rate of braking
resistor.