8 Applied Settings
Bias Adjustment of Analog Output
Terminal
Ao1
Ao2
You can bias Point 0 as shown in the below figure.
(V):(mA)
10 :20
[Bias]=0.0(%)
-5: -10
(Ex.) Outputting information on the "[dA-01] output frequency monitor" to [Ao1] in a voltage range from
0 to 10 V
Output in a range from 0 Hz to the maximum frequency (60 Hz).
[Cd-23]=0.0%, [Cd-24]=100.0%
(V)
10
5
0
0Hz
(Ex.) Outputting information on the output frequency monitor to [Ao1] in a current range from 4 to 20 mA
Output in a range from 0 Hz to the maximum frequency (50 Hz).
[Cd-23]=20.0%, [Cd-24]=80.0%
(mA)
20
10
4
0
0Hz
[Cd-23]=20.0(%)
8 - 182
Common to voltage/current
Common to voltage/current
[Bias]=50.0(%)
5:10
Parallel
movement
0: 0
Maximum
0
[Bias]=-50.0(%)
Output frequency (Hz)
Maximum frequency
30Hz
60Hz
[Cd-24 ]=8 0.0 (%)
Output frequency (Hz)
Maximum frequency
25Hz
50Hz
Current/voltage
Outputting will
be made in this
range.
Output scale
High-function General-purpose Inverter RX2 Series User's Manual
Bias parameter
[Cd-23]
[Cd-33]