• When [AA115] Stop mode selection is set to 00: Deceleration stop
FOC
FW
Output
frequency
current flows.
• When [AA115] Stop mode selection is set to 01: Free run stop
FOC
FW
Restart after free-run stop
Output
frequency
current flows.
 Parameter
Item
Input terminal func-
tion
STOP mode
selection,
1st-motor
Restart mode after
FRS release
Retry wait time
before motor
restart
*1. See 7-5-3 Frequency Matching Start on page 7-65.
*2. See 7-5-4 Frequency Pull-in Start on page 7-69.
Precautions for Correct Use
• If torque at starting is insufficient, it may improve by adjusting the boost amount at starting
[HC111], [HC112] or the speed response [HA115].
• See 7-1 Overview of Motor Control Methods on page 7-3.
• If torque at starting is insufficient, it may improve by using the torque bias function. See 7-3-6
Torque Bias Function on page 7-54.
High-function General-purpose Inverter RX2 Series User's Manual
Excitation current does
Deceleration
Excitation
stop
Excitation current does
Excitation
Free-running
Parameter
Data
[CA-01] to
066
[CA-11]
00
[AA115]
01
00
01
[bb-40]
02
[bb-26]
0.3 to 100.0(s)
The inverter does not run
because FOC terminal =
OFF.
not flow.
The inverter does not run
because FOC terminal =
OFF.
not flow.
Description
Forcing function [FOC]
Performs the deceleration stop when the opera-
tion command is off.
Performs the free-run when the operation com-
mand is off.
Performs the 0 Hz restart.
Performs frequency matching restart.
Performs frequency pull-in restart.
Sets the wait time after the operation command.
7 Advanced Settings
Default
data
-
00
*1
00
*2
0.3
7 - 79
7