A frequency command uses [AHD] in the analog input.
AHD
Analog input
Frequency command
 Parameter
Item
Main speed command
selection
Input terminal function
selection

6-4-13 Temporal Change of Frequency Command Destinations

When [F-OP] terminal is ON, the frequency destination can be changed temporally.
When 023 [F-OP] terminal is ON, the command destination of [CA-70] is employed in a priority to the
frequency command destination given in [AA101].
Precautions for Correct Use
When 023 [F-OP] terminal is ON, the operation command destination also employs the opera-
tion command selection designated in [CA-71].
 Parameter
Item
Input terminal function
selection
Speed reference
source selection at
[F-OP] is active
RUN command source
selection at [F-OP] is
active
High-function General-purpose Inverter RX2 Series User's Manual
ON
Parameters
Data
[AA101]
01 to 15
[CA-01] to
019
[CA-11]
Parameters
Data
[CA-01] to
023
[CA-11]
[CA-70]
01 to 15
[CA-71]
00 to 06
6 Basic Parameter Settings
ON
Description
01: Ai1-L input, 02: Ai2-L input, 03: Ai3-L input
AHD: Analog command holding
Description
[F-OP]: Gives a forced command.
01: Ai1-L input, 02: Ai2-L input, 03: Ai3-L input,
04: (Reserved), 05: (Reserved), 06: (Reserved),
07: parameter setting,
08: RS485 communication, 09:option 1,
10: option 2, 11: option 3,
12: pulse string input (main body),
13: pulse string input (option)
14: program function, 15: PID arithmetic
00: [FW]/[RV] terminal, 01: 3 wire,
02: RUN key on LCD operator,
03: RS485 communication, 04: option 1,
05: option 2, 06: option 3
6
Default
data
-
01
00
6 - 43