Dc Voltage Monitor [D102]; Regenerative Braking Load Rate Monitor [D103]; Electronic Thermal Load Rate Monitor [D104] - Omron SYSDRIVE MX2 SERIES User Manual

Multi-function compact inverter
Hide thumbs Also See for SYSDRIVE MX2 SERIES:
Table of Contents

Advertisement

DC Voltage Monitor [d102]

The Inverter P-N DC voltage (DC voltage between the Inverter terminals P/+2 and N/-) is
displayed.
During operation, the monitor value changes depending on the actual DC voltage of the
Inverter.
Parameter
No.
d102

Regenerative Braking Load Rate Monitor [d103]

Displays a regenerative braking load rate. When the displayed value exceeds the value set in
Usage Rate of Regenerative Braking (b090), the Inverter trips because of "E06 (Braking
resistor overload protection)".
Parameter
No.
d103
Related functions

Electronic Thermal Load Rate Monitor [d104]

Displays an electronic thermal load rate. When the displayed value exceeds 100%, the Inverter
trips because of "E05 (Overload protection)".
When the power is shut off, the displayed value changes to 0. Also when totaling does not
occur for 10 minutes, the displayed value changes to 0.
Parameter
No.
d104
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)
Function name
DC Voltage
0.0 to 999.9/1000.
Monitor
Function name
Regenerative Braking
0.0 to 100.0
Load Rate Monitor
Function name
Electronic Thermal Load
Rate Monitor
Data
Data
b090
Data
0.0 to 100.0
5-1 Monitor Mode
Default
Unit
setting
V
Default
Unit
setting
%
Default
Unit
setting
%
5-12