"D" Group: Monitoring Functions
3-3-30 Regenerative Braking Load Rate Monitor [d103]
3-3-31 Electronic Thermal Monitor [d104]
3-3-32 Analog Input O/OI Monitors [d130/d131]
3-3-33 Pulse Train Input Monitor [d133]
86
Displays a regenerative braking load rate. When the displayed value exceeds
the value set in the Usage Rate of Regenerative Braking (b090), the inverter
trips beacuse of "E06 (Braking resistor overload protection)".
Parameter
Function name
No.
d103
Regenerative braking
load rate monitor
Related functions
Displays an electronic thermal load rate. When the displayed value exceeds
100%, the inverter trips because of "E05 (Overload protection)".
When the power is shut off, the displayed value changes to 0. Also when
totaling does not occur for 10 minutes, the displayed value changes to 0.
Parameter
Function name
No.
d104
Electronic thermal
monitor
Displays the analog input O/OI value. The data range is from 0 to 1023 and it
can be read from Modbus and Drive Programming.
Parameter
Function name
No.
d130
Analog input O monitor
d131
Analog input OI monitor
The pulse train input monitor (terminal EA) is always valid, independently of
any parameter setting. This monitor shows the value after full scale conver-
sion and filter processing but before bias addition.
Parameter
Function name
No.
d133
Pulse train input monitor
Data
0.0 to 100.0
b090
Data
0.0 to 100.0
Data
0 to 1023
Data
0.00 to 100.00
Section 3-3
Default
Unit
setting
-
%
Default
Unit
setting
-
%
Default
Unit
setting
-
-
Default
Unit
setting
-
%