Communication with the PLC
6.5.3
External single measurement via external inputs
Measurement start
Function result
Function fault
OUT warning
(0-sheet, 1-sheet, 2-sheet)
BOUT warning
(0-sheet, 1-sheet, 2-sheet)
Fig. 41: Timing diagram for external single measuring via external inputs
1)
In case of "Function fault" = 1 "Function result" will sometimes remain at 0.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
90
Double Sheet Detector R1000-series I20
with integrated fieldbus interface
IN / BIN
BOUT
1)
BOUT
BOUT
Ready
The operation of the individual measurement, which is initiated via the
Note
external input, can be controlled via the process channel, see section
"6.3.2 Start single measurement via process channel". If no control is
done via the process channel, then the measurement operation must be
controlled by the signal "ENABLE", see section "6.5.1 Signal ENABLE".
Manual
"1" in case of fault
"0" in case of fault
„0" active
„0" active
< 15 ms
B0060191 / Rev. 1.7
< 15 ms