Roland R1000 Series Manual page 116

Double sheet detector with integrated fieldbus interface
Hide thumbs Also See for R1000 Series:
Table of Contents

Advertisement

Start-up
Program parameter 5: Setting the percentage threshold of the lower limit value.
Program Parameter: 5
lower threshold
Fig. 71: Adjusting the upper limit
Value range: between 0% and 99%
Program parameter 6: Setting the percentage threshold of the upper limit value.
Program Parameter: 6
upper threshold
Fig. 72: Adjusting the lower limit
Value range: between 100% and 180%
Program parameter 7: Adjusting the nominal settling time and indicating the actual settling time.
Program Parameter: 7
settling time I20
desired value:250ms
actual value: 250ms
Fig. 73: Adjusting the nominal settling time
In the upper line the „desired value" of the settling time must be entered. If the achievable settling
time exceeds the „desired value", the system selects the next larger possible value and indicates
this value in the line below.
Possible choices:
2 / 4 / 8 / 15 / 25 / 100 / 250 ms
In general, the „desired value" should be set such that it fits the transportation speed and the sheet
length.
Fast transportation and short sheets require shorter measurement times
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
116
Double Sheet Detector R1000-series I20
with integrated fieldbus interface
80%
120%
Manual
B0060191 / Rev. 1.7