Double sheet detector with integrated fieldbus interface
Hide thumbs Also See for R1000 Series:
Table of Contents

Advertisement

B0060191 / Rev. 1.7
6.5.1
Signal "Enable"
The signal "ENABLE" corresponds with the two process channel signals BOUT "Ready" and BOUT
"Function fault" according to the following Boolean logic.
ENABLE = BOUT Ready
BOUT
Ready
BOUT
Function fault
Fig. 40: Boolean function "ENABLE"
If the signal BOUT "Ready" is reset, then a fault has occurred, which requires a user intervention at
the control unit. Possible causes: memory faults, missing or too low voltages.
6.5.2
Signal "Warning"
The "Warning" signal is an additional output signal with fixed evaluation thresholds.
The signal becomes activated if the measurement result is below 80% or above 120% of the preset
nominal value.
Application: If the warning signal is activated though a sheet is between the sensors, measuring
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Double Sheet Detector R1000-series I20
with integrated fieldbus interface
BOUT Function fault
&
ENABLE
The timing diagrams in the sections "6.5.3" and "6.5.4" do not contain an
Note
explicit chart of the signal "ENABLE".
problems might have been occurred:
Sensor distance changed
Sheet too close to the transmitter / receiver
Wrong type of sheet
Sensor coverage not sufficient (3 × sensor diameter)
If these requirements are met, but a warning signal is issued, then the
Note
Teach-In must be repeated. The requirements from section "4.3 Sensor
mounting" should be observed.
The signal will also be activated if measurements without a sheet
Note
(measurement value below 80%) are performed.