System Parameter: 18
automat.Prog.select.
Fig. 111: Setting the method of program selection
Possible choices:
no:
yes:
System parameter 19: Setting the monitoring of the PLC voltage.
System Parameter: 19
In/Out PLC Voltage
no monitoring
Fig. 112: Setting the monitoring of the PLC voltage
Possible choices:
no monitoring
monitoring
If the parameter is set to "monitoring" and the PLC voltage is not connected, a respective fault
message will be indicated.
Remedy: connect the voltage and then confirm the fault message.
System parameter 20: Deactivating / activating the external adjust via fieldbus.
System Parameter: 20
external adjust
Fig. 113: Deactivating / activating the external adjust
Here the external adjust, which is possible via fieldbus with the signals "Teach-In" and "zero
adjust", can be deactivated / activated.
Possible choices:
yes
no
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Double Sheet Detector R1000-series I20
with integrated fieldbus interface
no
When the program is switched via Fieldbus or I/O, the program number will not be
stored. So the system always starts up with the program which was last selected by
keyboard operation.
When the program is switched via Fieldbus or I/O, the program number will be
stored. After applying power the system always starts up with the program which
was stored last.
If the program is switched often, the memory becomes loaded with
Attention
frequent writing cycles and thus becomes destroyed during the
time (lifetime approx. 1.000.000 write cycles).
In this case „no" should be selected here.