Table 10-28 PM240-2, IP20, frame size F, 380 V ... 480 V 3 AC
Article No. without filter
Article No. with filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Fuse according to IEC
Fuse according to UL, class J
Power loss without filter
Power loss with filter
Required cooling air flow
Weight without filter
Weight with filter
Table 10-29 PM240-2, IP20, frame size F, 380 V ... 480 V 3 AC
Article No. without filter
Article No. with filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Fuse according to IEC
Fuse according to UL, class J
Power loss without filter
Power loss with filter
Required cooling air flow
Weight without filter
Weight with filter
Converter with the CU250S-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG
6SL3210-1PE31-5UL0
6SL3210-1PE31-5AL0
75 kW
140 A
145 A
55 kW
117 A
110 A
3NA3140 (200 A)
200 A
1.91 kW
1.93 kW
153 l/s
57 kg
63 kg
6SL3210-1PE32-5UL0
6SL3210-1PE32-5AL0
132 kW
242 A
250 A
110 kW
218 A
205 A
3NA3252 (315 A)
350 A
2.98 kW
3.02 kW
153 l/s
61 kg
65 kg
10.3 Technical data, PM240-2 Power Modules
6SL3210-1PE31-8UL0
6SL3210-1PE31-8AL0
90 kW
172 A
178 A
75 kW
154 A
145 A
3NA3142 (224 A)
250 A
2.46 kW
2.48 kW
153 l/s
57 kg
63 kg
Technical data
6SL3210-1PE32-1UL0
6SL3210-1PE32-1AL0
110 kW
198 A
205 A
90 kW
189 A
178 A
3NA3250 (300 A)
300 A
2.28 kW
2.30 kW
153 l/s
61 kg
65 kg
463