Advertisement

Alarms, faults and system messages
8.6 List of alarms and faults
Number
Cause
F01512
An attempt has been made to es‐
tablish a conversion factor for scal‐
ing which does not exist
A01590
Motor maintenance interval elapsed Carry out maintenance and reset the maintenance interval (p0651).
F01600
STOP A initiated
F01625
Sign-of-life error in the Safety data
F01650
Acceptance test required
F01659
Write task for parameter rejected
F01662
Error, internal communications
A01666
Static 1 signal at the F-DI for safe
acknowledgement
A01698
Commissioning mode active for
safety functions
A01699
Switch-off signal path test required
F01800
DRIVE-CLiQ: Incorrect hardware/
configuration
402
Remedy
Create scaling or check transfer value.
Select STO and then deselect again.
● Check the electrical cabinet design and cable routing for EMC
compliance.
● Check whether an impermissible voltage is connected at one of the
digital outputs.
● Check whether a digital output is loaded with an impermissible current.
● Check whether additional faults exist and perform diagnostics if
applicable.
● Select STO safety function and then deselect again.
● Switch off the inverter power supply and switch it on again.
Carry out an acceptance test and create test certificate.
Switch off the Control Unit and switch on again.
Cause: The inverter should be reset to the factory setting. However, it is
not permissible to reset the safety functions as the safety functions are
currently enabled.
Remedy with operator panel:
p0010 = 30
Parameter reset
p9761 = ...
Enter password for the safety functions.
p0970 = 5
Reset start safety parameter.
The inverter sets p0970 = 5 once it has reset the param‐
eters.
Then reset the inverter to the factory setting again.
● Check the electrical cabinet design and cable routing for EMC
compliance.
● Check whether an impermissible voltage is connected at one of the
digital outputs.
● Check whether a digital output is loaded with an impermissible current.
If the checks are unsuccessful:
● Switch off the inverter power supply and switch it on again
● Upgrade the firmware
● Contact technical support
Set fail-safe digital input F-DI to a logical 0 signal.
This message is withdrawn after the Safety commissioning has ended.
After the next time that the "STO" function is deselected, the message is
withdrawn and the monitoring time is reset.
A DRIVE-CLiQ connection error has occurred.
Check the DRIVE-CLiQ cables at the Control Unit.
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG
Converter with the CU250S-2 Control Units