Analog Inputs - Siemens SINAMICS G120 Operating Instructions Manual

Low voltage inverters built-in units with cu250s-2 control units and encoder evaluation
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Advanced commissioning
6.3 Adapt the default setting of the terminal strip
6.3.3

Analog inputs

Overview
Connector inputs are marked with "CI" in the parameter list of the List Manual.
Defining the analog input type
The inverter offers a series of default settings, which you can select using parameter p0756:
AI 0
AI 1
In addition, you must also set the switch associated with the analog input. You
can find the switch on the Control Unit behind the lower front door.
● Voltage input: Switch position U (factory setting)
● Current input: Switch position I
170
Interconnecting signals in the inverter (Page 503)
Unipolar voltage input
Unipolar voltage input monitored
Unipolar current input
Unipolar current input monitored
Bipolar voltage input
No sensor connected
Unipolar voltage input
Unipolar voltage input monitored
Unipolar current input
Unipolar current input monitored
Bipolar voltage input
No sensor connected
The parameter p0756[x] and the switch on the
inverter specify the analog input type.
Define the function of the analog input by inter‐
connecting parameter p0755[x] with a connec‐
tor input CI of your choice.
0 V ... +10 V
+2 V ... +10 V
0 mA ... +20 mA
+4 mA ... +20 mA
‑10 V ... +10 V
---
0 V ... +10 V
+2 V ... +10 V
0 mA ... +20 mA
+4 mA ... +20 mA
‑10 V ... +10 V
---
Converter with the CU250S-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG
p0756[0] =
0
1
2
3
4
8
p0756[1] =
0
1
2
3
4
8