4.5.11.4

Installing GSDML

Procedure
1. Save the GSDML to your PC.
– With Internet access:
– Without Internet access:
2. Unzip the GSDML file on your computer.
3. Import the GSDML into the engineering system of the controller.
You have now installed the GSDML in the engineering system of the controller.
4.5.12

Connecting the inverter to PROFIBUS

The PROFIBUS DP interface has the following functions:
● Cyclic communication
● Acyclic communication
● Diagnostic alarms
General information on PROFIBUS DP can be found in the Internet:
support/printkatalog.htm)
Converter with the CU250S-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG
GSDML (http://support.automation.siemens.com/WW/view/en/22339653/133100)
Insert a memory card into the inverter.
Set p0804 = 12.
The inverter writes the GSDML as zipped file (*.zip) into directory /SIEMENS/SINAMICS/
DATA/CFG on the memory card.
PROFIBUS user organization (http://www.profibus.com/downloads/installation-guide/)
Information about PROFIBUS DP
4.5 Connecting the interfaces for the inverter control
(http://www.automation.siemens.com/net/html_76/