Siemens SINAMICS G120 Operating Instructions Manual page 345

Low voltage inverters built-in units with cu250s-2 control units and encoder evaluation
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

The inverter compares speed r0586 with the actual speed value r2169 and signals an
excessive deviation between the encoder signal and the motor speed. p2181 specifies the
inverter response for an excessive deviation.
Parameter
p0490
p0580
p0581
p0582
p0583
p0585
r0586
p2181
p2192
p2193 = 2
p3230 = 586
p3231
The "Probe" subfunction calculates the speed from the pulse signal of the digital input.
1)
For more information, see the List Manual (the parameter list and function diagram 8013).
Converter with the CU250S-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG
Description
Probe
invert (factory setting 0000bin)
1)
The 3rd bit of the parameter value inverts the input signal of digital input 3 for the
probe.
Probe
Input terminal (factory setting 0)
1)
Connect input of probe with a digital input.
Probe
Edge (factory setting 0)
1)
Edge for analyzing the probe signal for measuring the actual speed value
0: 0/1 edge
1: 1/0 edge
Probe
Pulse per revolution (factory setting 1)
1)
Number of pulses per revolution
Probe
Maximum measurement time (factory setting 10 s)
1)
Maximum measurement time for the probe If there is no new pulse before the maxi‐
mum measuring time elapses, the inverter sets the actual speed value in r0586 to
zero.
The time is restarted with the next pulse.
Probe
Gear ratio (factory setting 1)
1)
The inverter multiplies the measured speed by the gear ratio before displaying it in
r0586.
Probe
Actual speed value
1)
Result of the speed calculation
Load monitoring response
1: A07920 for torque too low
2: A07921 for torque too high
3: A07922 for torque outside tolerance
4: F07923 for torque too low
5: F07924 for torque too high
6: F07925 for torque outside tolerance
Load monitoring delay time (factory setting 10 s)
Delay time for evaluating load monitoring.
Load monitoring configuration (factory setting: 1)
0: Monitoring switched off
1: Monitoring torque and load drop
2: Monitoring speed and load drop
3: Load failure monitoring
Load monitoring actual speed value (factory setting 0)
Result of the speed calculation with the evaluation of the speed monitoring.
Load monitoring speed deviation (factory setting 150 rpm)
Permissible speed deviation of load monitoring.
Advanced commissioning
6.28 Monitoring the driven load
343