Siemens SINAMICS G120 Operating Instructions Manual page 194

Low voltage inverters built-in units with cu250s-2 control units and encoder evaluation
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Advanced commissioning
6.5 Drive control via PROFIBUS or PROFINET
Status word 3 (ZSW3)
Bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
192
Meaning
1 = DC braking active
1 = |n_act | > p1226
1 = |n_act | > p1080
1 = i_act ≧ p2170
1 = |n_act | > p2155
1 = |n_act | ≦ p2155
1 = |n_act | ≧ r1119
1 = DC link voltage ≦ p2172
1 = DC link voltage > p2172
1 = ramp-up or ramp-down completed Ramp-function generator is not ac‐
1 = technology controller output at the
lower limit
1 = technology controller output at the
upper limit
Not used
Not used
Not used
Not used
Description
--
Absolute current speed > stationary
state detection
Absolute actual speed > minimum
speed
Actual current ≥ current threshold
value
Absolute actual speed > speed
threshold value 2
Absolute actual speed < speed
threshold value 2
Speed setpoint reached
Actual DC link voltage ≦ threshold
value
Actual DC link voltage > threshold
value
tive.
Technology controller output ≦
p2292
Technology controller out‐
put > p2291
Converter with the CU250S-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG
Signal intercon‐
nection in the in‐
verter
p2051[3] = r0053