Siemens SINAMICS G120 Operating Instructions Manual page 373

Low voltage inverters built-in units with cu250s-2 control units and encoder evaluation
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Procedure with the BOP-2
You have now safely removed the memory card using BOP-2.
Converter with the CU250S-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG
1. Set p9400 = 2.
If a memory card is inserted, p9400 = 1.
2. The inverter sets p9400 = 3 or p9400 = 100.
● p9400 = 3: You may remove the memory card from the inverter.
● p9400 = 100: It is not permissible that you remove the memory card.
Wait for several seconds and then set p9400 = 2 again.
3. Remove the memory card. After removing the memory card, p9400 = 0.
Saving the settings and series commissioning
7.1 Saving settings on a memory card
371