Advanced commissioning
6.22 Electrically braking the motor
Set dynamic braking
Parameter
p0219
p2106
An example for configuring a drive with braking resistor is provided in the Internet:
support.industry.siemens.com/cs/de/en/view/103156155)
324
Description
Braking power of the braking resistor (factory setting: 0 kW)
For p0219 > 0, the inverter deactivates the VDC_max controller.
For vector control, p0219 specifies the regenerative power limit p1531.
Set with p0219 the maximum braking power that the braking resistor must handle.
The inverter extends the ramp-down time of the motor when the braking power is too low.
You can find the technical data of the braking resistor in the Power Module hardware
installation manual.
Overview of the manuals (Page 519)
The SIZER PC tool provides support for calculating the braking power.
Configuring support (Page 521)
BI: External fault 1
p2106 = 722.x
Engineering and commissioning series lifting equipment/cranes
Monitor the signal for overtemperature of the braking resistor with dig‐
ital input x of the inverter.
Connecting the temperature contact of the braking resistor
(Page 113)