Technical data
10.4 Technical data, PM250 Power Module
10.4.3

Specific technical data, PM250

Note
The values for Low Overload (LO) are identical with those of the rated values.
Table 10-38 PM250, IP20, Frame Size C, 3-ph. AC 380 V ... 480 V
Article no.
LO base load output
LO base load input current
LO base load output current
HO base load output
HO base load input current
HO base load output current
Fuse
Power loss
Required cooling air flow
Weight
Table 10-39 PM250, IP20, Frame Size D, 3-ph. AC 380 V ... 480 V
Article no.
LO base load output
LO base load input current
LO base load output current
HO base load output
HO base load input current
HO base load output current
Fuse according to IEC
Fuse according to UL
Power loss
Required cooling air flow
Weight
Table 10-40 PM250, IP20, Frame Size E, 3-ph. AC 380 V ... 480 V
Article no.
LO base load output
LO base load input current
LO base load output current
474
6SL3225-0BE25-5AA1
7.5 kW
18 A
18 A
5.5 kW
13.2 A
13.2 A
20 A, Class J
0.24 kW
38 l/s
7.5 kg
6SL3225-0BE31-5AA0
18.5 kW
36 A
38 A
15 kW
30 A
32 A
3NA3820
50 A, Class J
3NE1817-0
0.44 kW
22 l/s
15 kg
6SL3225-0BE33-0AA0
37 kW
70 A
75 A
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG
6SL3225-0BE27-5AA1
11 kW
25 A
25 A
7.5 kW
19 A
19 A
32 A, Class J
0.30 kW
38 l/s
7.5 kg
6SL3225-0BE31-8AA0
22 kW
42 A
45 A
18.5 kW
36 A
38 A
3NA3822
63 A, Class J
3NE1818-0
0.55 kW
22 l/s
15 kg
6SL3225-0BE33-7AA0
45 kW
84 A
90 A
Converter with the CU250S-2 Control Units
6SL3225-0BE31-1AA1
15 kW
32 A
32 A
11 kW
26 A
26 A
35 A, Class J
0.31 kW
38 l/s
7.5 kg
6SL3225-0BE32-2AA0
30 kW
56 A
60 A
22 kW
42 A
45 A
3NA3824
80 A, Class J
3NE1820-0
0.72 kW
39 l/s
16 kg