Terminal strips behind the upper front door

Figure 4-14
Interconnection example of the digital inputs with external 24 V power supply
All terminals with reference potential "GND" are connected with one another in the inverter.
Connecting the optional 24 V supply to terminals 31, 32 has the following advantages:
● The Control Unit remains in operation after disconnection of the Power Module from the
line supply. The Control Unit thus maintains the fieldbus communication, for example.
● You can use terminals 51 ... 54 as digital outputs.
→ for terminals 31, 32 only use a 24 VDC power supply with PELV (Protective Extra Low
Voltage).
→ for applications in the USA and Canada: Use a 24 VDC power supply, NEC Class 2.
Converter with the CU250S-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG
4.5 Connecting the interfaces for the inverter control
Installing
93