An overview of all the parameters that belong to the command data sets is provided in the List
Manual.
Note
It takes approximately 4 ms to toggle between command data sets.
Changing the number of command data sets
Procedure
1. Set p0010 = 15.
2. The number of command data sets is configured with p0170.
3. Set p0010 = 0.
You have changed the number of command data sets.
Copying command data sets
Procedure
1. Set p0809[0] to the number of the command data set whose settings you wish to copy
(source).
2. Set p0809[1] to the number of the command data set in which you wish to copy the settings.
3. Set p0809[2] = 1
4. The inverter sets p0809[2] = 0.
You have copied the settings of a command data set into another command data set.
Parameter
Parameter
p0010
r0050
p0170
p0809[0]
p0810
p0811
Converter with the CU250S-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG
6.12 Switching over the drive control (command data set)
Description
Drive commissioning parameter filter
Command data set CDS active
Displays the number of the currently active command data set
Number of command data sets (CDS) (factory setting: 2)
p0170 = 2, 3 or 4
Copying the command data set CDS (factory setting: 0)
[0] Source command data set
[1] Target command data set
[2] 0→1: Starts the copy operation
Command data set selection CDS bit 0
Command data set selection CDS bit 1
Advanced commissioning
219