Advanced commissioning
6.14 Free function blocks
PDE (ON delay)
I
T
Q
Runtime group
Run sequence
PDF (OFF delay)
I
T
Q
Runtime group
Run sequence
232
The rising edge of a pulse at input I sets output Q = 1 after
pulse delay time T.
When I = 0, then the function block sets Q = 0.
PDE 0
PDE 1
p20158[0]
p20163[0]
p20159
p20164
r20160
r20165
p20161
p20166
p20162
p20167
When I = 1, then the function block sets Q = 1.
The falling edge of a pulse at input I sets output Q = 0 after
OFF delay time T.
When input I returns to 1 before time T has expired, output
Q remains 1.
PDF 0
PDF 1
p20168[0]
p20173[0]
p20169
p20174
r20170
r20175
p20171
p20176
p20172
p20177
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG
PDE 2
PDE 3
p20334[0]
p20339[0]
p20335
p20340
r20336
r20341
p20337
p20342
p20338
p20343
PDF 2
PDF 3
p20344[0]
p20349[0]
p20345
p20350
r20346
r20351
p20347
p20352
p20348
p20353
Converter with the CU250S-2 Control Units