Siemens SINAMICS G120 Operating Instructions Manual page 165

Low voltage inverters built-in units with cu250s-2 control units and encoder evaluation
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Table 6-2
Commands for switching the motor on and off
ON
The inverter switches the motor on.
Jogging 1
Jogging 2
Enable operation
OFF1, OFF3
The inverter brakes the motor. The inverter switches off the motor once it comes to a standstill.
The motor is considered to be stationary if the speed is less than a defined minimum speed.
OFF2
The inverter switches off the motor immediately without first braking it.
Inhibit operation
Parameter
Parameter
Description
p1226
Standstill detection, speed
threshold [rpm]
p1227
Standstill detection monitor‐
ing time [s]
p1228
Pulse cancellation delay time
[s]
Further information
You will find additional information in function diagram 2610 of the List Manual.
Converter with the CU250S-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG
6.2 Sequence control when switching the motor on and off
Setting
Factory setting: 20.00
rpm
Factory setting: 300.00
s
Factory setting: 0.01 s
Advanced commissioning
The inverter identifies that the motor is at a
standstill after OFF1 or OFF3 when at least one
of the following conditions has been satisfied:
● The speed actual value falls below the
threshold in p1226 and the time started in
p1228 has expired.
● The speed setpoint falls below the threshold
in p1226, and the time subsequently started
in p1227 has expired.