Configuring A Safety Function - Siemens SINAMICS G120 Operating Instructions Manual

Low voltage inverters built-in units with cu250s-2 control units and encoder evaluation
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Advanced commissioning
6.17 Safe Torque Off (STO) safety function
6.17.2.2

Configuring a safety function

Procedure
1. Select "Select safety functionality".
2. Select "Basic Functions".
3. Select "Control type/safety functions".
4. Select "Via terminals" as control type for the safety functions.
You have configured the safety functions.
Additional configurations of the safety functions are described in the "Safety Integrated"
Function Manual.
Parameter
p0010 = 95 Drive commissioning parameter filter
p9601
248
Overview of the manuals (Page 519)
Description
Safety Integrated commissioning
Enable functions integrated in the drive (factory setting: 0000 bin)
0 hex
None of the safety functions has been released
1 hex
Basic functions via onboard terminals has been enabled
Converter with the CU250S-2 Control Units