Installing
4.5 Connecting the interfaces for the inverter control
4.5.11.3

What do you have to set for communication via PROFINET?

Configuring PROFINET communication in the I/O controller
You require the appropriate engineering system to configure PROFINET communication in
the IO controller.
If required, load the GSDML file of the inverter into the engineering system.
Device name
In addition to the MAC address and IP address, PROFINET also uses the device name to
identify PROFINET devices (Device name). The device name must be unique across the
PROFINET network.
To assign the device name, you need an engineering software, e.g. HW-Config or STARTER.
The inverter saves the device name on the inserted memory card.
IP address
In addition to the device name, PROFINET also uses an IP address.
You have the following options to specify the IP address of the inverter:
● You specify the IP address via an engineering software, e.g. via HW-Config or STARTER.
● The IO Controller assigns an IP address to the inverter.
Telegram
Set the same telegram in the inverter as in the IO Controller. Interconnect the telegrams in the
control program of the IO Controller with the signals of your choosing.
Application examples
You can find application examples for PROFINET communication on the Internet:
PROFINET or PROFIBUS, with Safety Integrated (via terminal) and HMI
support.industry.siemens.com/cs/ww/en/view/60441457)
PROFINET or PROFIBUS, with Safety Integrated (via terminal) and HMI
support.industry.siemens.com/cs/ww/en/view/78788716)
116
Installing GSDML (Page 117)
Drive control via PROFIBUS or PROFINET (Page 183)
Controlling the speed of a SINAMICS G110M/G120/G120C/G120D with S7-300/400F via
Controlling the speed of a SINAMICS G110M / G120 (Startdrive) with S7-1500 (TO) via
Converter with the CU250S-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG