Siemens SINAMICS G120 Operating Instructions Manual page 405

Low voltage inverters built-in units with cu250s-2 control units and encoder evaluation
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Number
Cause
A01900
PROFIBUS: Configuration tele‐
gram faulty
A01910
Setpoint timeout
F01910
A01920
PROFIBUS: Cyclic connection in‐
terrupt
F03505
Analog input, wire break
A03520
Temperature sensor fault
A05000
Power Module overtemperature
A05001
A05002
A05004
A05006
F06310
Supply voltage (p0210) incorrectly
set
F07011
Motor overtemperature
A07012
I2t motor model overtemperature
A07015
Motor temperature sensor alarm
F07016
Motor temperature sensor fault
F07086
Switching over units: Parameter lim‐
F07088
it violation
F07320
Automatic restart aborted
Converter with the CU250S-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG
Remedy
Explanation: A PROFIBUS master is attempting to establish a connection
with a faulty configuration telegram.
Check the bus configuration on the master and slave side.
The alarm is generated when p2040 ≠ 0 ms and one of the following causes
is present:
● The bus connection is interrupted
● The Modbus master is switched off
● Communications error (CRC, parity bit, logical error)
● An excessively low value for the fieldbus monitoring time (p2040)
Explanation: The cyclic connection to PROFIBUS master is interrupted.
Establish the PROFIBUS connection and activate the PROFIBUS master
with cyclic operation.
Check the wiring for interruptions.
Check the level of the injected signal.
The input current measured by the analog input can be read out in r0752.
Check that the sensor is connected correctly.
Check the following:
- Is the ambient temperature within the defined limit values?
- Are the load conditions and duty cycle configured accordingly?
- Has the cooling failed?
Inverter protection using temperature monitoring (Page 327)
Check the set supply voltage and if required change (p0210).
Check the line voltage.
Reduce the motor load.
Check ambient temperature.
Check the wiring and connection of the sensor.
Check and if necessary reduce the motor load.
Check the motor's ambient temperature.
Check the thermal time constant p0611.
Check overtemperature fault threshold p0605.
Check that the sensor is connected correctly.
Check the parameter assignment (p0601).
Make sure that the sensor is connected correctly.
Check the parameterization (p0601).
Deactivate the motor temperature sensor fault evaluation (p0607 = 0).
Check the adapted parameter values and if required correct.
Increase the number of restart attempts (p1211). The current number of
start attempts is shown in r1214.
Increase the wait time in p1212 and/or monitoring time in p1213.
Connect an ON command (p0840).
Increase the monitoring time of the power unit or switch off (p0857).
Reduce the wait time for resetting the fault counter p1213[1] so that fewer
faults are registered in the time interval.
Alarms, faults and system messages
8.6 List of alarms and faults
403